Technical Specifications and Certifications
26
5.9 Racking Rules - Clearance Requirements
The following table lists the racking rules and clearance requirements.
Table 10: Clearance Requirements
Area
Recommended Minimum Clearance
Front of the rack
36" (90 cm) for technician access and maintenance
Rear side of the rack
24" (60 cm) for human accessibility
Sides of the rack
No limits
Space below the chassis
No limits
Space on top of the chassis
No limits
5.10 Power Data
5.10.1 Type of Power Cord on the Power Supply
With each Power Supply, Mellanox provides a 15Amp cord (2 meter jumper), with a universal
plug for a PDU (Power Distribution Unit). This cord is detachable from the Grid Director 4200
Power Supply. Cable wiring: 3x14AWG.
5.10.2 Power Requirements
The following table provides the Grid Director 4200 power requirement specifications.
Table 11: Grid Director 4200 Power Requirements
Item
Description
Power Supply Modules (sPSU-S)
with N:1 or N:N redundancy.
Note: each Power Supply has its
own power cord.
Up to 4 Power Supplies
Electrical Rating
100-120/200-240V, 50-60Hz, 60A
12/8A per power feed MAX
Typical Power
Consumption (QDR full
configuration)
2000 Watt
Leakage current @254 V [mA]:
>6mA RMS (Note that leakage exceeds 3.5mA when more than one
power supply is being used)
Indicators
Operational AC and DC Status LEDs
Operating voltage
100-240 VAC, 50-60 Hz auto-sensing
Power factor
0.98 typical at 230 VAC, full load
0.98 typical at 115Vac, full load
Temperature rating
0-45 degrees Centigrade
5.10.3 Power Characteristics
The following table details the Grid Director 4200 single power supply characteristics.